TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
2-71.
CARTRIDGE FILTER MAINTENANCE - continued.
INSTALLATION
a.
Apply anti-seize tape to male pipe threads. Be sure tape is wrapped in same direction as pipe threads.
b.
Install elbow (6) on cartridge filter (1).
c.
Install adapter (31) and pipe section (12) on cartridge filter (1).
d.
Position two gasket halves (21) on deck (20). Aline holes with threaded inserts in deck.
WARNING
Installation of cartridge filter requires the use of a crane rated at 1 ton (0.91 ton) or greater in order to
prevent damage to the equipment and injury to personnel.
e.
Using lifting equipment and two assistants, lower cartridge filter assembly (1) and position on ROWPU deck.
Aline mounting holes with holes in gasket halves (21)
f.
Install four bushings (22), four flat washers (23), four lockwashers (24), and four screws (25).
g.
Position bracket (30) and install two flat washers (29), screws (28), lockwashers (2), and two nuts (3).
h.
Install system piping removed to aid replacement of cartridge filter (1) (para 2-38).
i.
Install hose (27) on nipple (47) and tighten hose clamp (26).
j.
Position pipe section (18) and tighten union (19).
k.
Install gasket (16), clamp halves (15), two screws (17) and nuts (14).
l.
Install gasket (32), clamp halves (33), two screws (34) and nuts (35).
m.
Install gasket (11), clamp halves (10), two screws (13) and nuts (9).
n.
Install tubing (7) on elbow and adapter (8).
o.
Install flexible tubing (4) on elbow (6) and tighten hose clamp (5).
p.
Connect flexible tubing (36) and fasten quick-disconnect (37).
q.
Install cover plate (para. 2-36).
r.
Operate ROWPU (TM 10-4610-240-10). Check for leaks and proper operation.
2-260