ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
0011 00
OPERATOR INSTRUCTIONS
DESCRIPTION & USE OF OPERATOR CONTROLS & INDICATORS
4
2
3
1
5
ITEM
CONTROLS AND INDICATORS
FUNCTION
1
RO Reject Flow Transmitter FT-401.
Works with Flow Element FE-401 in the RO System to measure the
reject flow from the RO vessels. Reject flow is displayed at the
operator control panel (OCP).
2
Conductivity Indicating Transmitter (Analyzer)
Uses inputs from Conductivity Elements CE-501A and CE-501B in the
CIT-501.
RO System and provides an output to the PLC to determine total
dissolved solids (TDS) in the product water. Product TDS is displayed
at the OCP.
3
Conductivity Transmitter ON/OFF switch.
low EMI and to turn the transmitter on as required for conductivity data
collection.
4
MF Feed Flow Transmitter FT-101
Works with Flow Element FE-101 in the MF System to measure the
MF flow (feed flow to the MF assembly when filtering, backwash flow to
the MF assembly during backwash). This flow is displayed at the
operator control panel (OCP).
5
Product Flow Transmitter FT-501.
Works with Flow Element FE-501 in the RO System to measure
product flow. The flow is displayed at the OCP.
0011 00-12