ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
0011 00
OPERATOR INSTRUCTIONS
DESCRIPTION & USE OF OPERATOR CONTROLS & INDICATORS
RAW WATER SYSTEM CONTROLS AND INDICATORS
1
5
4
2
3
12
7
13
9
11
8
10
14
6
Table 10. Raw Water System Controls.
ITEM
CONTROLS AND INDICATORS
FUNCTION
1
PRIMING VALVE V-102.
Part of Adapter A-02. Used to vent air when priming the raw water pump
2
DRAIN VALVE V-103 (P-1 DIESEL PUMP).
Used to Drain P-1 Pump for maintenance and at the end of the mission.
3
DRAIN VALVE V-105 (P-2 MOTOR-
Allows for draining of the P-2 Motor-Driven Raw Water Pump for
DRIVEN RAW WATER PUMP)
maintenance or at the end of the mission.
4
CYCLONE SEPARATOR FLOW CONTROL
Controls the flow of the raw water, carrying the sand from the separator.
VALVE V-104.
Part of Adapter A-03.
5
MANUAL FLOW CONTROL VALVE V-107
Raw water flow valve. Manually adjusted to maintain proper level of raw
water in the MF feed tank. Part of Adapter A-05.
6
P-1 DIESEL PUMP ENGINE
First pump in the raw water system when two pumps are required.
7
FUEL CAP
Allows for adding diesel fuel to P-1 Diesel Engine.
8
FUEL COCK
Allows for opening and closing of the fuel flow to P-1 Diesel Engine.
9
FUEL DRAIN PLUG
Allows for removing diesel fuel from P-1 Diesel Engine Fuel Tank.
10
OIL LEVEL DIP STICK
Displays oil level in P-1 Pump Diesel Engine.
11
RECOIL STARTER HANDLE
Allows for manual starting of P-1 Diesel Engine.
12
ENGINE DECOMPRESSION LEVER
Relieves P-1 Diesel Engine compression for starting.
13
ENGINE CONTROL LEVER
Controls the engine speed of P-1 Diesel Engine.
14
OIL DRAIN PLUG.
Allows for draining oil in P-1 Pump Diesel Engine.
0011 00-13