ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0021 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
MICRO-FILTRATION SYSTEM CLEANING OPERATION UNDER
USUAL CONDITIONS
CLEANING WASTE TANK
A-16
A-10
A-16
TOP
VALVE V-706
VALVE V-706
2 X 10 S-HOSES
VIEW OF
TWPS
4 X 5 S-HOSE
A-12
VALVE V-705
Figure 5. MF Acid Cleaning Waste Hose Set-Up with the Cleaning Waste Tank.
e. If not using the cleaning waste tank, set up the cleaning waste hoses as follows (see
Figure 6):
1) Connect a 2 x 10, red-banded, cleaning waste suction hose to Adaptor A-10.
2) Connect one 50-foot, green banded, raw water discharge hose to the 2 x10, red-
banded cleaning waste hose.
3) Connect one 2x10, red-banded, cleaning waste suction hose to the other end of
the 50-foot hose.
4) Connect Adaptor A-12 to the end of the second cleaning waste hose.
5) Close Adaptor A-12 Valve V-705.
6) Direct A-12 discharge into a depression in the ground away from the TWPS.
A-10
TOP
VIEW OF
TWPS
2 X 10 S-HOSE
4 X 5 S-HOSE
2 X 50 D-HOSE
A-12 VALVE V-705
2 X 10 S-HOSE
Figure 6. MF Acid Cleaning Waste Hose Set-Up Without the Cleaning Waste Tank.
2. Set valves for MF acid cleaning as follows (see Figure 7 for valve location):
a. Close MF Vent Valve V-114.
b. Open MF Clean Feed Valve V-704.
c. Be sure that Clean Return Valve V-702 is open.
d. Be sure that Clean Mixing Valve V-703 is closed.
e. Close MF Filtrate Drain Valve V-203.
f. Close MF Shell Drain Valve V-403.
g. Be sure that Adaptor A-12 Valve V-705 on the cleaning waste hose is closed (see Figure
5 or Figure 6 for valve location).
0021 00-8