ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0027 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
OPERATION UNDER UNUSUAL CONDITIONS
NBC TANK
NBC HYPOCHLORITE TUBE
PRODUCT HOSE P02
RD
3
TWPS UNIT
RD
3 TWPS UNIT RAW WATER PUMP
DISTRIBUTION SYSTEM
WITH DISTRIBUTION PUMP INLET
HOSE P04
ST
ND
COUPLING FROM 1 OR 2 UNIT
DISTRIBUTION PUMP
PRODUCT HOSE P02
PRODUCT HOSE P02
SHARED 6K
DISTRIBUTION TANKS
ST
ND
1
TWPS UNIT
TWPS UNIT
2
Figure 11. Double Pass NBC Filtration Set-Up Using Three TWPS Units.
5. Operate the first two TWPS units for the first filtration pass as follows:
a. Unless treating water contaminated with cyanide, set the Speed dial on the hypochlorite
pump to OFF (fully counterclockwise).
b. If treating water contaminated with cyanide, set up the hypochlorite chemical system after
water production is established (with the product hose disconnected from the A-15
adaptor) as follows:
1) Hypochlorite is not used. In its place, AC-350 caustic is used to increase the pH
of the product water to a value of 10.5 to 11. This improves the rejection of the
cyanide when the product water is treated in the second pass operation.
2) Record the product water TDS and flow rate after start up.
3) Calculate the amount of AC-350 caustic required in milliliters to be added when
filling the chemical bucket:
Factor A = Product TDS (in mg/L) x 0.141 + 9.8
Amount = 2.97 x Factor A x Product Flow (gpm)
4) Use the Bisulfite chemical bucket (blue cover) in place of the hypochlorite bucket.
Fill the bucket with product water from the utility hose to the 4.5-gallon mark.
5) Prime Chemical Pump CP-3 following the procedure for normal operation (WP
6) Set the Speed to 70 and the stroke to 60.
0027 00-15