ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0045 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR MAINTENANCE PROCEDURES
GENERAL MAINTENANCE
c.
Install the flexible coupling over the gasket and install the bolts and nuts but do not
tighten.
d. Inspect the coupling and gasket to ensure that the gasket is properly fitted around the
piping and not in the coupling grooves. Rotating the coupling back and forth will set the
gasket.
e. Tighten the coupling nuts and bolts.
Pipe Coupling Replacement:
Parts:
Pipe Coupling (TM 10-4610-309-24P)
Materials:
Clean, dry lint-free rags (WP 0079, Table 1, item 23)
Corrosion preventive compound (WP 0079, Table 1, item 12)
Equipment Condition:
TWPS in Standby Shutdown with Drain-Down
Replace an pipe coupling as follows (see Figure 5):
1. Make sure the TWPS is in Standby Shutdown with Drain-Down. Refer to WP 0017.
2. Remove the pipe coupling as follows:
a. Remove the nuts and bolts that secure the clamps to the pipe joint at both ends of the
pipe joint. Remove the clamps and set aside.
b. With a screw driver and hammer, tap the gasket retainers loose from the gaskets at both
ends. Push the pipe joint and gasket back onto one of the pipes until it clears the end of
the other pipe.
c. Remove pipe support clamps and loosen other connections as needed to free one or
both pipes to move or rotate enough to move the ends clear of each other. Remove the
gaskets, gasket retainers and pipe joint from the pipes.
PIPE JOINT
GRIPPERS (2)
NUT
GASKET
BOLT
PIPE END
GASKET RETAINER
CLAMP
Figure 5. Pipe Coupling Replacement.
0045 00-5