ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0048 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
RAW WATER SYSTEM
Cyclone Separator Repair / Replacement:
Parts (TM 10-610-309-24P):
Cyclone separator
Gaskets
Material:
Equipment Condition:
TWPS removed from service
Inspect the cyclone separator for leaks, cracks or other damage. Refer any metal repairs to Direct
Support maintenance. Inspect the couplings for damage and damaged or missing gaskets and replace
as necessary, using sealing compound on the coupling threads. Replace the entire assembly if the
separator has excessive leakage, if structural damage is significant enough that the assembly cannot be
repaired, or if the separator is inoperable.
REPAIR
P-1 and P-2 Pump Overhaul:
Parts (TM 10-4610-309-24P):
Kit, Pump Overhaul
Flapper Assembly
Outlet Flange Gasket
Material:
Corrosion Preventive Compound (WP 0079, Table 1, item 17)
Equipment Condition:
Pump assembly removed from service
Pump Overhaul
This section provides instructions for overhauling the P-1 or P-2 pump by replacing the internal
components. A pump should be overhauled if its flow rate has noticeably decreased, or if inspection of
the pump during disassembly for some other maintenance task (such as engine/motor replacement)
shows that the impeller or wear plate is damaged or badly corroded. Additional instructions in this
section describe how to replace the pump inlet flapper assembly and the outlet flange gasket.
NOTE
Whenever the P-1 or P-2 pump is disassembled for any of the maintenance tasks in
this work package, replace the drive sleeve, seal seat, seal assembly, and housing
gasket regardless of their condition. These components are included in the seal
repair kit. The overhaul kit includes these components plus the impeller, wear
plate, and wear plate mounting screws and gaskets.
0048 00-17