OPERATING
INSTRUCTIONS
RECEIPT OF MATERIEL
Section I. SERVICE UPON
strainer to
one
end
of
(4) Attach
2-1. Inspecting and
Servicing the Equipment
hypochlorinator suction hose (5 foot length) and
a, Inspection.
place in hypochlorite bag (solution reservoir),
(1) Check unit for breaks, cracks, or other
attach other end of hose to hypochlorinator suction
possible shipping damage.
fitting.
(2) Check to determine if all attachments
(5) Attach one end of waste water hose (8 foot
required for operation are present and in an
length ) to hypochlorinator adapter. Place the other
operating condition.
end at a point away from the apparatus.
b. Servicing.
(6) Connect hypochlorinator discharge hose
(1) Thoroughly clean all surfaces with an
( 2 0 - i n c h length) between hypochloqrinator
approved cleaning solvent. Wash with potable
discharge fitting and hose connector at inlet
water.
coupling.
(2) Perform required preventive maintenance
b. The unit is equipped with 2-inch female pipe
checks and services.
connections at the inlet and outlet that can be
connected directly into main water line or the line
a. Refer to figure 2-1 and install the component
to be treated. In some cases, adapters are furnished
as follows:
to permit a 3-inch hose inlet connection and a 4-
(1) Lift reservoir support from stowed position
inch pipe discharge connection. The outlet con-
so that it lies parallel to floor.
nection must be connected to the line which runs to
(2) Insert hypochlorite bag (solution reservoir)
the storage tank or distribution system. Figure 2-2
and attach straps to hooks on reservoir support.
illustrates water flow after installation of unit into
(3) Attach one end of inlet hose (4 foot length)
main line.
t o petcock adapter and place other end in
.
hypochlorite bag (solution reservoir).