TM 5-4610-218-12
Table 4-2. Troubleshooting-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Check for leaks between the flow indicator and the water source.
Step 2.
Eliminate all leaks.
Step 3. Check for air in the piping.
Bleed water to free air.
Step 4.
Check for clogged flow indicator piping.
Clean or replace the piping.
CHEMICAL FEED EQUIPMENT
CHEMICAL SOLUTION FEEDER WILL NOT OPERATE.
6.
Step 1.
Check for a defective electric cable.
Inspect for burned out motor.
Step 2.
Replace the chemical solution feeder motor, paragraph 4-20 (Raider Model
Step 3. Check for broken internal shafts or gears.
Replace the chemical solution feeder, paragraph 4-20 (Raider Model only-
7.
CHEMICAL SOLUTION FEEDER PUMPS INSUFFICIENT OR NO SOLUTION.
Step 1. Check to see if the solution supply is exhausted.
Check for loose feed wingnuts.
Step 2.
Step 2.1. (Raider Model only) Check for loose control knob thumbscrews.
Reset control knob adjustments and tighten thumbscrews.
Step 3. Check for clogged supply lines.
Remove and clean the lines.
4-47
Change 3