TM 5-4610-223-12
Table 3-1.Operator/Crew Preventive Maintenance Checks and Services - Cont
NOTE: Within designated interval, these checks are to be performed in the order listed.
B - Before
A - After
M - Monthly
D - During
W - Weekly
C - Combat Operability Check
Interval
Item to be
Procedures
Equipment will
Item
Inspected
Check for and have repaired
be reported Not
No.
B
D
A
W
M
C
or adjusted as necessary.
Ready (Red) if:
18
Circuit
Inspect the circuit breaker
Circuit breaker
Breaker
for cracks in the case, and
is defective or
test the toggle to make sure
missing.
it has a distinct snap when
it is operated.
19
Start-Stop
Inspect the terminal lugs
Switches are
Control
for looseness or damaged
found defective.
threads.
Inspect the
switches for cracks and
faulty pushbuttons.
20
Wet Well
Inspect the globe and recep-
Indicator
tacle for cracks and other
Light
damage.
21
Buzzer
Inspect buzzer for cracks
or other damage.
22
Power
Inspect the receptacle con-
Receptacles
nector for cracks, and
burned or loose terminal
lugs and for failure to hold
the plug connector firmly
when it is inserted.
23
*
Electrical
Inspect door hinge for
Control
operating condition and
Panel
cabinet assembly for
Circuit
obvious damage.
3-9