TM 5-4610-223-12
Table 3-1.Operator/Crew Preventive Maintenance Checks and Services - Cont
NOTE: Within designated interval, these checks are to be performed in the order listed.
B - Before
A - After
M - Monthly
D - During
W - Weekly
C - Combat Operability Check
Interval
Item to be
Procedures
Equipment will
Item
Inspected
Check for and have repaired
be reported Not
No.
B
D
A
W
M
C
or adjusted as necessary.
Ready (Red) if:
37
Erdlator
Inspect the shaft for misalignment
Agitator
Inspect the pillow blocks for
Drive Shaft
cracks and rough or noisy bearings.
Assembly
Inspect for worn keys and keyways.
38
Erdlator
Inspect the speed reducer for leaks,
Drive Gear
cracks, worn keyways, shaft end
Speed
play and noisy operation.
Reducer
39
Filter Pump
Inpsect the motor for signs of
Filter Pump and
and Motor
overheating and damaged electrical
Motor Assembly
Assembly
cable. Inspect the pump for binding
Is found
and damaged or cracked housing
defective
40
Raw Water
Inspect the motor for signs of
ltaw Water l'unil
Pump and
overheating and damaged electrical
and Motor
Motor
cable Inspect the pump for blinding
Assembly
Assembly
and damaged or cracked housing
are found
defective
41
Hoses and
Inspect hoses for holes, cracks or
Class III
Fittings
abrasions. Inspect fittings for
Leakage Is
cracks, dents, or stripped threads.
found
42
Heater
Inspect the controls for damage
Controls
With the heater operating, inspect
for proper operation.
Change 5 3-12