TM 55-1930-209-14&P-1
Table 13-3. ROWPU System Valves (continued)
Label Identification
Type
Valves
Location
and Valve Function
3-in.
RO11
ROWPU space - in
CARTRIDGE FILTER TO HIGH
gate valve
HP pump suction line
PRESSURE PUMP; Allows filtered
seawater from cartridge filter
assembly to flow to HP pump
3-in.
RO12
ROWPU space - in-
BRINE TO OVERBOARD
gate valve
board of pretreatment
DISCHARGE; allows brine to
skid
flow overboard from RO block
when making product water
3/4-in.
RO13
ROWPU space - near
MEMBRANE CLEANING
2-way
membrane cleaning
SOLUTION RETURN; allows flow
ball valve
solution drum
of membrane cleaning solution
back to drum
3/4-in.
RO14
ROWPU space - near
MEMBRANE CLEANING
2-way
membrane cleaning
SOLUTION INPUT; allows
ball valve
solution drum
membrane cleaning solution
to flow from drum
3-in.
RO15
ROWPU space - be-
PRODUCT WATER TO STORAGE
gate valve
tween RO block and
TANKS; allows product water
HP pump
from RO block to flow to
drinking water storage tank
3-in.
RO16
ROWPU space - between
HIGH PRESSURE PUMP BYPASS;
gate valve
RO block and HP pump
allows flow of membrane cleaning
solution to RO block bypassing HP
pumps
1/4-in.
RO17
ROWPU space - in
BRINE SAMPLING; for
2-way
brine discharge piping
taking samples of brine
ball valve
near valve RO7
output from RO block
3-in.
RO18
ROWPU space - in
SEAWATER TO ROWPU;
gate valve
pretreatment skid
allows flow of seawater to
seawater Input piping
ROWPU pretreatment skid
3-in.
RO19
ROWPU space - inboard
MEMBRANE CLEANING
gate valve
(Barges
of pretreatment skid
SOLUTION RECIRCULATION;
2 and 3
during RO block membrane
only)
cleaning, allows cleaning
solution to recirculate
through seawater pump
3-in.
RO20
ROWPU space - between
PRODUCT WATER TO
gate valve
(Barges
RO block and HP pump
OVERBOARD; allows flow of
2 and 3
product water from RO block to
only)
overboard
4-in.
R021
Void 3 port shell
PRODUCT WATER
gate valve
(Barges
OVERBOARD DISCHARGE;
2 and 3
allows product water from RO
only)
block and RO 20 to flow overboard
13-22