TM 55-1930-209-14&P-19
Table 9-3. Preventive Maintenance Checks and Services for Electrical Power Systems(Continued)
B - Before
D - During
A - After
H - Hourly Interval
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A
H
AS NECESSARY
250 hrs
9)
When coolant is at proper level and
level stabilizes, replace radiator cap.
250hrs
n. Check tubes in heat exchanger expan-
sion tank for scaling.
1)
If obstructed or scaled, clean tubes by
passing a rod slightly smaller than the
internal tube bore thru the tubes. Do
not use excessive force.
2)
If expansion tank tubes are so
clogged that a rod cannot be passed
thru them, completely remove the
core and clean by boiling in a caustic
soda solution or with a commercial
cooling system cleaner.
3)
Reassemble the heat exchanger and
activate.
o. Remove red tag from generator switch-
board.
500 hrs
a. Service primary and final fuel filters by
performing the following:
1)
Redtag affected SSG on switchboard
panel indicating, "WARNING-DO
NOT ACTIVATE. REPAIRS BEING
MADE."
2)
Shut off fuel tank supply valve on
engine.
3)
Loosen nut on top center of primary
filter body. Lower filter case.
4)
Remove filter element. Wash both ele-
ment and filter case in clean, non-
flammable solvent.
5)
Reinstall element in reverse order.
6)
Remove and discard final filter ele-
ment by turning from left to right
(right- hand thread).
7)
Remove all old gasket material. Clean
gasket sealing surface in filter mount.
9-19