TM 55-1930-209-14&P-19
Table 16-4. Preventive Maintenance Checks and Services
for Ventilation, Heating, and Air Conditioning System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
3
Fans and Motors
WARNING
Always make sure that electrical power is
OFF before performing any maintenance
on electrical systems. Redtag appropri-
ate switches and circuit breakers with:
"WARNING - DO NOT ACTIVATE.
REPAIRS BEING MADE." Observe all
safety precautions listed at the beginning
of this manual.
a. Visually inspect fans and motors for dam-
Fans or motors
age. damaged.
b. Check fan blades for sufficient cleanli-
Fan blades do not
ness and clearance. Clean as necessary.
have sufficient
clearance.
c.
Check that electrical connections are
tight. Tighten or repair as necessary
using insulated tools.
d. Listen for and check any fan or motor
which indicates a motor overload condi-
tion or unusual vibration which could
result in or be caused by bad bearings,
broken impeller blades, or housing shut-
down and notify shift leader for repair or
replacement.
e. Visually check deckhouse roof fans for
corrosion or damage. Repair as neces-
sary.
f.
Check all fans and motors for rust and
corrosion. Remove with wire brush and
paint as necessary in accordance with
TB 43-0144. Do not paint threads or
labels.
16-13