TM 55-1930-209-14&P-5
d.
Supplying storage tank drinking water to pressure set for use onboard barge - paragraph 3-7.
e.
Filling drinking water reserve tank - paragraph 3-8.
f.
Supplying drinking water onboard barge from reserve tank- paragraph 3-9.
g
Supplying drinking water to dayroom, washdown stations, chlorination unit, and shower - paragraph 3-10.
3-4.
Filling drinking water storage tanks
a. Open appropriate drinking water valves as shown in table below. Make sure valves of tank(s) not to be filled
are closed.
To fill drinking water storage tank
Open valves
1
DW1, DW6
2
DW2, DW7
3
DW3, DW8
4
DW4, DW9
b.
Close drinking water valves DW11, DW12, and DW18 (Barges 2 and 3 only) and make sure drinking water
valves DW10 and DW13 are closed.
NOTE
Storage tanks are now ready to be filled with water from ROWPU 's.
c.
Make sure chlorine Is being added to the ROWPU product water before water enters storage tanks. If
chlorination system Is not operating, start up by following procedures In TM 55-1930-209-14&P-4.
NOTE
EMS monitors and indicates water level in each storage tank (Figure
3-5) and amount of chlorine in water entering tanks.
d.
Make sure EMS Is operating and monitoring water level in each tank and amount of chlorine In water entering
tanks If not, start up by following procedures in TM 55-1930-209-14&P-11.
NOTE
Water level in each tank is also shown on each tank's liquid level
indicator.
e.
As tanks are being filled, periodically check EMS video monitor POTABLE WATER TANKS display page for
water levels and CHLORINE STATUS display page to make sure chlorine input Is 5 to 7 ppm.
NOTE
If water level rises above full level In tank(s) as shown on EMS video
monitor, horn and strobe light in ROWPU space are activated and
buzzer In dayroom sounds. In addition, EMS keyboard alarm
sounds and video monitor automatically switches to ALARM page
which shows full tank levels alarm condition In flashing double
intensity. POTABLE WATER TANKS key on keyboard flashes red.
f.
When alarms are energized, stop filling tanks.
g.
Press red flashing POTABLE WATER TANKS key on keyboard to change ALARMS display page back to
POTABLE WATER TANKS alarm display page.
h.
Press ACK key on keyboard to stop alarms and automatically change red flashing POTABLE WATER TANKS
key to white and flashing display on video monitor POTABLE WATER TANKS page to double intensity.
NOTE
Display stays double intensity until abnormal condition is corrected.
3-9