TM 55-1930-209-14&P-5
Tank
1
2
3
4
Valve no:
DW6
DW7
DW8
DW9
b.
Open valve DW11
c.
Close reserve tank valve DW13
d.
Close power panel 1 circuit breaker 11 P5 to provide power to drinking water pressure set motor controller
e.
Prime water pressure set as follows, If necessary.
(1) Position HAND/OFF/AUTO switch on pressure set motor controller to HAND.
(2) Start pressure set by pushing START button on motor controller
(3) Close valve DW16
(4) Open priming port petcock on pressure set
(5) Close petcock when steady flow appears
f.
Open drinking water valves DW5, DW5A (Barges 2 and 3 only), and DW17.
g.
Position pressure set motor controller HAND/OFF/AUTO to AUTO
NOTE
Pressure set automatically supplies on demand drinking water to dayroom fountain and sink, washdown stations in
ROWPU space and on deckhouse top, shower on forward weatherdeck, and void 2 port chlorination unit.
3-8.
Filling drinking water reserve tank
NOTE
Drinking water In reserve tank is for onboard use when drinking water Is not available from storage tanks
3-8.1.
Filling drinking water reserve tank from storage tanks
CAUTIONS
Water level in reserve tank must be checked daily by monitoring liquid level indicator. Add water if necessary. Chlorine
content must also be checked daily.
Obtain sample at reserve tank sample valve and check chlorine content according to TM 5-6630-215-12. Add chlorine
through chlorine fill on top of reserve tank if chlorine content is not between 2 and 5 ppm.
a.
Check liquid level indicator on storage tank(s) to make sure tank(s) contains drinking water
b.
Make sure pressure set motor controller HAND/OFF/AUTO switch is OFF
c.
Close valves DW13 and DW17
d.
Open valves DW11 and DW16
e.
Close power panel 1 circuit breaker 11 P5 to provide power to pressure set motor controller
NOTE
Pressure set automatically fills reserve tank.
f.
Position HAND/OFF/AUTO switch on pressure set controller to AUTO and pressure set automatically fills
reserve tank.
3-15