TM 55-1930-209-14&P-9-1
Table C-1. Preventive Maintenance Checks and Services for Electrical Power Systems (Continued)
B - Before
D - During
A - After
H - Hourly Interval
Interval
Procedures:
Equipment Is
Item
Item to be
Check for and have repaired
Not Ready/
No.
B D
A
H
Inspected
or adjusted as necessary
Available If:
4000 hrs
(c) Lubricate with grease gun, two
pumps. Use MPG. NLGI No. 2
grade is suitable for most temper-
atures. Use NLGI No. 1 or 0 grade
for extremely low temperatures.
(d) Install the lower plug. Wipe off
excess grease.
(e) Remove the fitting from the upper
threaded hole.
(f) Start the engine and allow the
grease to expand.
(g) Stop the engine. Install the plug in
the lower hole and wipe off excess
grease.
(h) Install the two panels.
3) To lubricate the inboard bearing,
remove the cowl cover from the rear
of the generator housing and:
(a) Remove the right side and lower
grease pipe plugs.
(b) Install a grease fitting in the right
side threaded grease pipe.
(c) Using a grease gun, lubricate tow
pumps. Use Multipurpose-type
Grease (MPG). NLGI No. 2 grade
is suitable for most temperatures.
Use NLGI No. 1 or 0 Grade for
extremely low temperatures.
(d) Install the lower plug. Wipe off
excess grease.
(e) Remove the fitting from the right
side grease pipe.
C-24