TM 55-1930-209-14&P-9-13-9.3 Restoration of normal source of electricity. When normal power is restored, 120 Vac electricity flows to outputside of inverter. Inverter ceases to operate, and 120 Vac, from normal power source, provides power directs b to emergencylighting panel. The 120 Vac also flows to battery charger, which recharges battery bank Battery bank continues to provide 24Vdc to DC power panel.SECTION III. Operating Instructions3-10. Operating controls and Indicatorsa. The 24 Vdc power panel in workshop contains eight circuit breakers and one used circuit (Figure 3-2).b. Emergency lighting panel, in ROWPU space on forward bulkhead, contains eight circuit breakers (Figure3-3).c. Battery charger in workshop (Figure 3-4) has HIGHFFLOAT switch on panel. HIGH setting activates fastcharging circuit in charger. FLOAT setting activates slower charging circuit than HIGH setting and maintainscharge in battery at all times. FLOAT is normal setting. When activating system after a shutdown of more than3 days, set on HIGH for not more than 24 hours.d. Battery charger panel displays a DC ammeter and DC voltmeter (Figure 3-4) that indicate charging rate andbattery status.e. Battery charger panel has ON/OFF switch that turns charger on or off.f. Battery charger panel has RESET button. When pressed it resets internal Circuit breakers on AC input and DCoutput circuits. Prior to resetting, troubleshoot emergency system to determine why circuit breakers were tripped.g. Inverter in workshop has ON/OFF switch that turns inverter on or off.3-11. Prestart checks. Before energizing emergency electrical system, perform following before operation preventivemaintenance services:WARNINGFumes from batteries may be flammable and explosive. Do NOT smoke or have open flame when checkingor working on battery bank.WARNINGBattery electrolyte presents potential health hazards. Contact with eyes and skin should be avoided. Safetyglasses, gloves, and rubber aprons must be worn when handling this chemical. Electrolyte contains sulfuricadd, which can cause severe bums, and Is highly toxic to skin, eyes, and respiratory system.a. Check batteries (Figure 3-5) for proper electrolyte level. Add distilled water or dean water to bring level above the plates.b. Check that battery bank is secure and that electrical cable fittings are tight and coated with anti corrosion grease. Correct as necessary.c. Check major components (inverter, battery charger, battery bank 120 Vac emergency panel, and DC panel) for damage and loose fittings or wires. Correct as necessary.d. Clean major components as necessary.e. Make sure that inverter switch is OFF.f. Make sure all circuit breakers on 120 Vac emergency panel and 24 Vdc panel are open.3-6
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business