Google+
Facebook
LinkedIn
Twitter
Digg
StumbleUpon
Home
Download PDF
Order CD-ROM
Order in Print
SECTION III. Operating Instructions - TM-55-1930-209-14P-9-1_58
Equipment specifications -cont - TM-55-1930-209-14P-9-1_60
TM-55-1930-209-14P-9-1 Water Purification Barges (NSN 1930-01-234-2165) Compressed Air System Manual
Page Navigation
36
37
38
39
40
41
42
43
44
45
46
TM 55-1930-209-14&P-9-1
Table 3-1. Major Components of Emergency Electrical System
Component
Location
Function
24 Vdc battery charger
Workshop
Keeps battery bank charged
DC-AC standby inverter
Workshop
Converts 24 Vdc from batteries to 115
Vac for emergency lighting panel
Battery bank
Deckhouse
Provides 24 Vdc to DC power panel and to
top forward
input side of inverter
24 Vdc power panel
Workshop
Provides 24 Vdc power for Army radio and
telephone system, foghorn,
bilge
alarm
module, emergency shutdown system,
and navigation and status lights
120 Vac emergency lighting panel
ROWPU space
Provides power to emergency lights in
forward bulkhead
deckhouse and voids, marine radio and
telephone buzzer system
3-5.
Equipment specifications
a.
Battery charger
Manufacturer
LaMarche Manufacturing Co.
CAGEC
92731
Part no.
A33-60-24 V
AC input
120 V, single ph, 60 Hz
DC output
24 V, 60 amps
Quantity
1
b.
DC to AC inverter
Manufacturer
LaMarche Manufacturing Co.
CAGEC
92731
Part no.
A51-1 .5K-24 V
Type
Manual
DC input
24 Vdc, 12.5 amps
AC output
115 Vac, 12.5 amps
Transfer
relay
2 to 10 KVA 40 msec
Quantity
1
c.
Battery
CAGEC
74309
Part no.
NS305
Type
Marine
Nominal voltage
6 V
Rate 2 capacity
305 amp/hrs
Quantity
4
d.
24 Vdc power panel
CAGEC
81349
Part no.
W3928/2-04-DP
Military specification
MIL-P-23928/2
Class
1
Rating
50 A, 120 Vac
Branches
8
Quantity
1
3-3
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business