TM 10-4320-317-13
(2)
Remove plastic cap from suction port (1) on pump. Retain cap for movement or storage.
(3)
Locate 6 in. X 10 ft lengths of rigid-walled, wire reinforced suction hose (2) with quick-disconnect fittings.
Figure 2-17. Boost Pumping Assembly
CAUTION
To prevent leakage, close both cam arms at the same time.
Do not strike cam arms to close. Damage to couplings could result.
(4)
Connect suction hose (2) to suction port (1). Close cam arms.
(5)
Install 6-inch butterfly valve (3) on suction hose (2) with 6-inch boltless coupling (4) (para. 2-8.b.). Set valve to
fully opened position.
(6)
Install lateral grooved wye-fitting (5) to 6-inch butterfly valve (3) with 6-inch boltless coupling (6).
(7)
Connect end of 10-mile segment hose (7) to lateral grooved wye-fitting (5) with 6-inch boltless coupling (8)
2-37