TM 10-4610-215-10
TM 08580A-10/1
(12) Operate ROWPU in normal manner (para. 2-25) and inspect cartridge filter for leaks. If there
are leaks, shut down ROWPU (para. 2-31) and tighten cover nuts or replace O-ring as applicable.
d. Removal (Model No. 600-3).
(1) Shut down ROWPU in the normal manner (see para. 2-31).
(2) Open VENT CARTRIDGE FILTER valve (fig. 2-56).
(3) Open DRAIN NO. 1 CARTRIDGE FILTER valve fully (para. 2-12).
(4) Loosen six eyenuts (1) and washers (2) from the cover brackets (3).
(5) Use quick disconnect and remove tubing from vent (6).
(6) Lift cover (4), remove O-ring (5) and hose on vent (6). Check O-ring for cracks, breaks and
hardening. Replace O-ring if bad.
LEGEND:
1. Eyenut
2. Washer
3. Bracket
4. Filter Cover
5. O-ring
6. Vent
7. Compression Plate
8. Tube Guides
9. Filter Tube
10. Sump Seat
Figure 3-11. Cartridge Filter Tube (Model No. 600-3)
(7) Remove compression plate (7) with tube guides (8).
3 - 28