Item
No.
11
12
13
14
TM 10-4610-215-10
TM 08580A-10/1
Table 2-3. Operator/Crew Preventive Maintenance Checks and Services
(Unit) (Continued)
B Before
D -During
A - A f t e r
W - Weekly
Interval
B
A
W
Item to be
inspected
Chemical feed
equipment: plastic
pails, tubes, and
strainers and
chemical cans
Chemical feed
pump
Chemical feed
pump motor
Chemical feed
pump priming
valves
Procedures
Check for and have repaired
or adjusted as necessary
Inspect container/rack, pails/cans
and tubes for cuts, cracks or holes.
Inspect during operation for leaks
Inspect strainer for clogging.
After operation, drain and
clean pails, tubes and strainers and
chemical cans.
Inspect for loose mounting
nuts.
Inspect for cracked or broken
fitting.
Check oil level before oper-
ation. Add oil as necessary.
Refer to LO 5461 0215-12/
LI 08580A12.
Listen for unusual noises
during operation.
Notify unit maintenance
to replace malfunctioning
pump. For sight glass
location and oil filling
instructions, see
lubrication order LO 10
4610-215-12/Ll 08580A12
Check for loose mounting
nuts and bolts.
Look for loose wires at conduit
box.
Listen for unusual noises
during operation.
Notify unit maintenance
to replace malfunctioning
motor.
Inspect for broken or missing
pipe nipples.
Check for free operation of
valve handles.
Check for chemical corrosion.
For readiness reporting
Equipment is not
ready/available
if:
Pails/cans are so
damaged that they will
not hold chemicals
Tubes will not
draw chemicals
into the pumps.
Any one of the
four pumps will
not supply chemical
to the purification
cycle.
Motor will not operate.
Valves will not
prime chemical
feed pump.
2-21