TM 10-4610-215-24
TM 08580A-24/2
(17) Press operating coil assembly (2) into bottom of cap (3) and seat firmly.
(18) Slide cap assembly (3) with operating coil assembly (2) attached, into top of base (20) and movable
contact assembly (13).
(19)
(20)
(20).
(21)
(22)
(23)
(24)
NOTE
Cap assembly may have to be gently moved from side to side to
allow guide (14) to slip into guide slots.
Seat cap (3) firmly onto top of base (20) mounting surfaces.
Install four screws (10), four lockwashers (11), and four flat washers (12) through cap (3) and base
NOTE
Remove identification tags from wires as wires are reinstalled.
Install wire (8) to overload relay T3 (9) and overload relay T2 (7).
Install wire (6) to overload relay T2 (7) and overload relay T1 (5).
Install wire (4) from overload relay T1 (5) to operating coil (2).
Install wire (1) from other side of operating coil to auxiliary switch on cap (3).
h. Test. (Refer to Schematic, Figure 112)
WARNING
ELECTRICAL HIGH VOLTAGE
Electrical high voltage can cause serious injury or death. Some
tests performed in testing require power to be connected. Always
take proper measures to ensure personal safety.
(1) Using the multimeter, check between upper and lower contacts of stationary contact assembly. It
should read open.
3-68