TM 10-4610-239-10
TM 08580B-10/1
Revolutions Per Minute..................................
500 (maximum)
Backwash Pump Motor
Voltage...........................................................
208230/460 V ac, 3-phase
Current ...........................................................
26.5-24/12 amp
Horsepower....................................................
10
Frequency ......................................................
60 Hertz
Revolutions Per Minute..................................
3450
Duty Cycle......................................................
Continuous
Backwash Pump
Type. ..............................................................
Centrifugal
Capacity .........................................................
120 gpm (454 Ipm) 70 psig
(49,217 kg/sqm)
Drive...............................................................
Electric motor
Revolutions Per Minute..................................
3500
Raw Water Pump Motor, 2 each
Voltage...........................................................
220230/460 V ac, 3-phase
Current ...........................................................
5.8/2.9 amp
Horsepower....................................................
2
Frequency ......................................................
60 Hertz
Revolutions Per Minute..................................
3450
Duty Cycle......................................................
Continuous
Raw Water Pump, 2 each
Type ...............................................................
Centrifugal, self-priming
Capacity .........................................................
30 gpm (114 Ipm) 105 ft
(32 m) head
Drive...............................................................
Electric motor
Revolutions Per Minute..................................
3500
Distribution and Booster Pump Motors
Voltage...........................................................
208-230/460 V ac, 3-phase
Current ...........................................................
3.4-3.2/1.6 amp
Horsepower....................................................
1
Frequency ......................................................
60 Hertz
Revolutions Per Minute..................................
3450
Duty Cycle......................................................
Continuous
Distribution and Booster Pumps
Type ...............................................................
Centrifugal
Capacity .........................................................
30 gpm (14 Ipm) 50 ft
(15 m) head
Drive...............................................................
Electric motor
Revolutions Per Minute..................................
3500
1-16