TM 10-4610-240-24
TM 08580C-24/2
TO 40W4-13-22
3-29.
CABLE ASSEMBLY W51 (BOOSTER PUMP) MAINTENANCE- continued.
p.
Remove locknut (8).
q.
Carefully pull booster pump cable assembly (3) and adapter (5) from electrical junction box (7).
r.
Remove adapter (5), sealing grip (4), nut (2) and O-ring (6) (discard O-ring) from booster pump cable
assembly (3) and remove cable from ROWPU.
INSPECTION
TEST
REPAIR
INSTALLATION
a.
Slide nut (2), sealing grip (4), adapter (5) and new -ring (6) on booster pump cable assembly (3).
b.
Pull booster pump cable assembly (3) through wall of electrical junction box (7) and position adapter (5).
c.
Install new O-ring (6) and locknut (8) on adapter (5).
d.
Install nut (2) on adapter (5).
e.
Working inside electrical junction box, position three wire lugs (12) as tagged, lug washers (12), and screws
(10) on bottom terminals of motor controller K6 (9).
f.
Position wire lug (14) on terminal (13) as tagged and secure with screw (15).
g.
Use wire ties to secure three wires to wire bundle on bottom and left wall of electrical junction box.
3-166