ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0004 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
PREPARATION FOR USE AND INSTALLATION INSTRUCTIONS
SITE SELECTION AND COMPONENT LOCATION
P-1 Pump Only Raw Water System Configuration (see Figure 3)
Diesel-driven pump P-1 can be used by itself when the elevation from the pump to the TWPS platform is
less than 25 ft. and the distance from the TWPS platform to the pump is less than 200 ft. The suction lift is
reduced below 23 ft. at temperatures above 70 degrees F. The main components used in this
configuration include the Diesel-Driven Pump P-1, Adaptor Assembly A-02, and up to four sections of 2
in. diameter by 50 ft. long discharge hose.
TOP VIEW
A-02
2 X 50 D-HOSE
P-1 PUMP
SIDE VIEW
Figure 3. P-1 Pump Only Raw Water System Configuration.
0004 00-5