ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0012 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
ESTABLISHING ELECTRICAL POWER OPERATION UNDER
USUAL CONDITIONS
PREPARING THE TWPS FOR POWER
Perform the following steps before starting the TQG.
1. (A-TWPS only) Make sure the bail bar is lowered (WP 0007)
2. Perform all "BEFORE" PMCS (preventive maintenance checks and services) listed in the PMCS
3. Place the fire extinguisher near the ground rod if not already moved to this location.
4. Set the Main Circuit Breaker (lever on the front of the Power Distribution Panel PDP) to OFF
(see Figure 3).
MAIN CIRCUIT BREAKER
Figure 3. Main Circuit Breaker OFF.
5. Set the following Operator Control Panel switches to the positions indicated:
a. Mode
to STANDBY
b. MF Clean
to OFF
c. Emergency Stop
to OUT
to OFF
e. Bisulfite Pump
to OFF
f. Antiscale/Chlorine
to AUTO
g. MF Test
to OFF
h. Hose/Pump Heaters
to OFF
i. Tank Heaters
to OFF
at the ON position (see Figure 3).
TACTICAL QUIET GENERATOR START-UP
WARNING
High voltage electrical hazard. Do not attempt to start the generator set if it has
not been properly grounded. Failure to observe this warning could result in
electrocution.
High voltage electrical hazard. High voltage is produced when the generator set is
in operation. Improper operation could result in personal injury or death.
0012 00-4