ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0012 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
ESTABLISHING ELECTRICAL POWER OPERATION UNDER
USUAL CONDITIONS
CAUTION
Potential starter damage. Do not crank the generator engine in excess of fifteen
seconds. Allow the starter to cool at least fifteen seconds between attempted
starts. Failure to observe this caution could result in damage to the starter.
1. Make sure all generator set access doors, except the control panel access door, are closed.
2. Start up the Tactical Quiet Generator (TQG) as described in TM 5-6115-545-12.
ENERGIZING THE TWPS POWER DISTRIBUTION PANEL
WARNING
Potential electrical hazard. Other personnel are setting up the raw water system of
the TWPS. Part of this set-up includes connecting raw water and MF feed pump
skid power cords to the PDP. Let the other set-up personnel know when you are
ready to make any pump power cable connections to the PDP. The panel may be
energized to power the air compressor (and the heater during cold weather
deployment) before the pump power cable connections are completed. The PDP
must be de-energized by switching the Main Breaker to OFF before making pump
power cable connections. Failure to observe this warning may result in injury or
death due to electrocution.
Energize the PDP as follows:
1. Perform the following notifications and checks:
a. Tell the other set-up personnel that you are ready to establish electrical power.
b. If the pump power cables are connected, check that the raw water and MF feed pump
power cable(s) has/have been properly connected at the pump skid(s) and at the PDP.
2. Energize the PDP as follows:
a. Switch the Main Circuit Breaker on the PDP to ON.
b. Check that the Power On light on the Operator Control Panel (OCP) is on. If it is not on,
check that the Emergency Stop button is pulled out.
c. If the alarm horn goes on, toggle the Alarm Switch to RESET to clear the power-up
alarms, then set the switch to SILENCE.
3. Notify the other set-up personnel that the PDP has been energized.
END OF WORK PACKAGE
0012 00-5/6 BLANK