MAINTAINING NORMAL OPERATION UNDER USUAL CONDITIONS
WARNING
Hazardous chemical and/or fumes. Wear the protective face shield and chemical
gloves when handling calcium hypochlorite solution. Avoid inhaling chemical
fumes. Hypochlorite will give off chlorine vapor, which will burn your nose, throat
and lungs if breathed directly. Direct contact with the eyes may cause severe eye
damage.
j.
Drain the pump.
k.
Take solution from the hypochlorite bucket and pour it into the pump discharge until the
pump is filled.
l. Reinstall Adaptor A-08 on the pump discharge.
m. Allow the pump to sit for 30 minutes.
n. Open the valve on Adaptor A-07.
o. Start the pump and flush it with product water for about one minute.
p. Stop the pump.
q. Close the valve on Adaptor A-07.
r. Install the distribution hoses and nozzles on Adaptor A-08.
13. Start up the TWPS. Refer to WP 0015.
WARNING
Health hazard. If a distribution pump is used in the raw water system, it must be sanitized
according to the sanitizing step above before it can used in the distribution system.
Failure to observe this warning could result in illness from contamination of the product
water.
END OF WORK PACKAGE