ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0024 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
MICRO-FILTRATION SYSTEM CLEANING WITH REVERSE OSMOSIS
SYSTEM ACID CLEANING OPERATION UNDER USUAL CONDITIONS
MF Acid Cleaning
1. Set valves for MF acid cleaning as follows (see Figure 10 for valve location):
a. Close MF Vent Valve V-114.
b. Open MF Clean Feed Valve V-704.
c. Be sure that Clean Return Valve V-702 is open.
d. Be sure that Clean Mixing Valve V-703 is closed.
e. Close MF Filtrate Drain Valve V-203.
f. Close MF Shell Drain Valve V-403.
g. Be sure that Adaptor A-12 Valve V-705 on the cleaning waste hose is closed (see Figure
5 or Figure 6 for valve location).
MF VENT VALVE V-114
CLEAN RETURN VALVE V-702
MF CLEAN FEED VALVE
V-704
CLEAN MIXING VALVE V-703
MF FILTRATE DRAIN
VALVE V-203
MF SHELL DRAIN
VALVE V-403
Figure 10. Valves for MF Acid Cleaning.
0024 00-11