ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0025 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
REVERSE OSMOSIS SYSTEM PRESERVATION OPERATION UNDER
USUAL CONDITIONS
2) Make sure the A-16 adaptor valve V-706 on the other side of the waste tank is
closed.
3) Disconnect Adaptor A-12 from the Adaptor A-16.
4) Direct the cleaning waste hose into an empty bucket, open Adaptor A-12 Valve
V-705 and drain the contents of the hose into the bucket.
5) Open the top of the waste tank and empty the bucket into the waste tank. Then
close the tank.
c. When drained, disconnect the cleaning waste hose from 4 x 2 Adaptor A-10.
d. Rinse the inside of the hose sections with water from the distribution system auxiliary
hose.
e. Remove 4 x 2 Adaptor A-10 from the 4-in. x 5-ft. waste out hose and rinse.
f. Remove the 4-in. x 5-ft. waste out hose from the waste discharge of the TPWS and rinse.
g. Remove the product utility hose from the RO feed tank.
PREPARATION FOR STORAGE
Perform the Preparation for Storage procedures as described in WP 0031, Preparation for Storage
Army Unit or as described in WP 0032, Preparation for Storage Marine Corps Unit.
END OF WORK PACKAGE
0025 00-15/16 BLANK