ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
OPERATOR INSTRUCTIONS
MICRO-FILTRATION SYSTEM PRESERVATION OPERATION UNDER
USUAL CONDITIONS
INITIAL SETUP
Materials/Parts:
AC-120 Bisulfite (1) 12 oz. Packet (Box #4)
Measuring Bottle for Bisulfite (Box #4)
Chemical scoop (Box #4)
AC-210 Citric Acid, (1) 20 lb. bucket
AC-350 Caustic, (2) 1 Gallon Containers (Box #5)
Three 2-in. x 10 ft. Cleaning Waste Hoses
Adaptor A-10 (Box #1)
Adaptor A-12 (Box #1)
Cleaning Waste Storage Module if used
One 1500 gallon cleaning waste storage tank
Two adaptors A-16 (A-TWPS, Box #1)
One 2 in. x 50 ft. raw water discharge hose if cleaning waste storage module not used
Personal protective gear (Box #1)
Two chemical aprons
One face shield
Two chemical gloves
One dust mask
Personnel Required:
Two Operators/Crew
Equipment Condition:
Short Term Shutdown WP0017 has been performed, the TQG and Air Compressor are left on
All drain and vent valves closed as instructed in WP0018.
All product 3-way valves set to normal operating position as instructed in WP0018.
WP0024 must be
completed prior to
performing MF Preservation in Preparation for Storage.
GENERAL
MF preservation procedures are performed when the TWPS is placed in an extended shutdown (shut
down longer than 54 hours during deployment) or when the TWPS is shut down in preparation for storage
(stand down from deployment).
Preservation is necessary to ensure that biological growth does not become established on the MF fibers
surfaces during the shutdown period. If they are not preserved and a biological film grows on the fibers,
the TWPS will not meet performance requirements when placed back in operation. If the biological
growth is severe enough, the MF modules will require extensive cleaning/soaking and may need to be
replaced.
The caustic used for MF Caustic Detergent Cleaning is used as the preservative for the MF. For an
extended shutdown, the caustic preservative solution is flushed through the MF module fibers once and
discharged into a cleaning waste holding tank. For a shutdown in preparation for storage, residual
caustic detergent cleaning solution left in the MF modules after the completion of the MF Caustic
Detergent Clean procedure serves to preserve the fibers until the next time the TWPS is deployed.
The procedures covered in this work package include:
MF Preservation Flush for Extended Shutdown
MF Preservation in Preparation for Storage (WP0024 procedures must first be performed)