ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0061 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
FEED FLOW CONTROL PANEL
ELECTRICAL CONNECTION
IP TRANSDUCER FY-102
ELECTRICAL CONNECTION
SCREWS,
LOCK
WASHERS
AND FLAT
WASHERS
IP TRANSDUCER FY-102
DISCONNECT TUBING HERE
TUBING
ADAPTERS
DISCONNECT TUBING HERE
DISCONNECT
TUBING HERE
Figure 4. IP Transducer FY-102.
2. Install the IP transducer into the feed flow control panel assembly as follows:
a. Apply antiseizing tape to the adapter threads.
b. Install the adapters in the new IP transducer in the same positions as they were in the old
transducer. Do not over-tighten.
c. Mount the IP transducer to the panel assembly, then install and tighten the two screws,
lock washers, and flat washers.
d. Connect the tubes that were disconnected from the old transducer to the same adapters
in the new transducer.
e. Reconnect the electrical connection to IP Transducer FY-102.
3. Check the feed flow control panel for proper operation and leaks.
0061 00-8