ARMY TM 10-4610-309-14
MARINE CORPS TM 10802A-14/1
0063 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
UNIT MAINTENANCE PROCEDURES
POWER DISTRIBUTION SYSTEM
UTILITY OUTLET
COVER
SCREW
OUTLET
NUT
WASHER
OUTLET COVER
SCREW
POWER DISTRUBUTION
BOX DOOR
Figure 15. Utility Outlet Assembly Replacement.
2. Install the new utility outlet assembly as follows:
a. Attach the wires to the screw connections on the new utility outlet in accordance to the
wire tags.
b. Tighten the screws to secure the wires.
c. Remove the wire tags.
d. Position the utility outlet on the power distribution box door and secure using the two
screws, washers, and nuts.
e. Position the outlet cover on the power distribution box door and secure using the four
screws, washers, and nuts.
f. Close the power distribution box door.
Light Switch Replacement:
Parts (TM 10-610-309-24P):
Selector Switch
Selector Switch
EMI Gasket
Equipment Condition:
TWPS in Standby Shutdown Without Draining Down
Army TWPS: Generator off and TWPS main breaker off
Marine Corps TWPS: TWPS disconnected from power source
0063 00-27