REVERSE OSMOSIS SYSTEM
REPLACE
RO Feed Tank Replacement:
Parts (TM 10-4610-309-24P):
RO Feed Tank
Pipe Coupling Gasket
4 In. Sanitary Clamp Gasket
21/2 In. Sanitary Clamp Gasket
2 3/8 In. Expansion Joint Gasket
2 In. Rubber Hose
1 7/8 In. Rubber Hose
Material:
Antiseizing tape (WP 0079, Table 1, item 43, 44)
Soap water solution
Equipment Condition:
TWPS in Short Term Shutdown with drain down (WP 0017)
Replace the RO feed tank as follows:
(Army only) Remove the TWPS skid from the flat rack. Refer to WP 0071.
Remove the RO feed tank as follows:
1.
Remove the TWPS frame cross braces at the right end of the TWPS as follows:
a. Remove the 4 bolts, 4 lock washers, and 4 flat washers from the 2 upper ends of the
frame cross braces at the right end of the TWPS.
b. Remove the 6 bolts, 12 flat washers, and 6 lock nuts from the middle of and the lower
ends of the cross braces.
c. Tag and remove the frame cross braces (see Figure 1).
FLAT
WASHER
LOCK
WASHER
BOLT
CROSS BRACES
Figure 1. TWPS Frame Cross Brace Removal Right End.
0070 00-2