ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0071 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
DIRECT SUPPORT MAINTENANCE PROCEDURES
TACTICAL WATER PURIFICATION SYSTEM (TWPS) SKID, FLAT RACK,
3. Install a TQG onto a flat rack as follows:
NOTE
When inserting a TQG onto the A-TWPS flat rack, make sure that the terminal
compartment of the TQG is facing into the flat rack toward the TWPS unit.
a. Using appropriate lifting equipment, lift and carefully insert the TQG onto the flat rack.
b. Make sure that the holes in the bottom framing of the TQG align with the holes in the floor
of the flat rack.
c. Secure the TQG to the floor of the flat rack using the through-bolts and nuts that were
removed earlier. Insert the bolts up through the bottom of the flat rack. (4 bolts, 8 flat
washers, 4 lock washers, and 4 nuts).
Frame, Tie-Down, and Lift Provision Repair:
Equipment Condition:
1. For repairs to the A-TWPS flat rack, remove the TPWS unit and TQG from the flat rack. Refer to
TWPS Removal from and Installation into the Flat Rack (A-TWPS Only) and TQG
Replacement (A-TWPS Only) in this work package.
2. For repairs to the TWPS frame, tie-down, or lift provisions perform the following:
a. (A-TWPS only) Remove the TWPS unit from the flat rack. Refer to TWPS Removal
from and Installation into the Flat Rack (A-TWPS Only).
b. Remove or protect components of the TWPS as necessary to perform required repairs.
3. For welding procedures, refer to TM 9-237 to weld damaged areas.
4. For painting of repaired areas, refer to TM 43-0139.
END OF WORK PACKAGE
0071 00-6