TM 10-4610-310-14
0004 00
CONTROL MODULE continued
Table 1. Control Module Controls and Indicators.
KEY
CONTROL OR INDICATOR
FUNCTION
1
POWER indicator (blue) (L5)
Indicates electrical power is ON, press
to test
2
CHEMICAL PUMPS ON/OFF/AUTO (SW10)
3-position selector switch to turn on/off
three chemical injection pumps P5, P6,
and P7 on the chemical
injection/cleaning module
3
RAW WATER PUMP OFF/ON switch (SW1)
2-position selector switch to turn on/off
service pump P1
4
RAW WATER PUMP indicator (green) (L1)
Indicates raw water service pump is
ON, press to test
5
MODE (1, 2, 3, 4) (SW8)
4-position selector switch used to set
the following functions: CYCLE,
BACKWASH, FAST FLUSH, or
MAINTENANCE on the UF module
6
Handle for main circuit breaker (CB1)
Used to turn circuit protection ON or
OFF and reset circuit breaker CB1
7
BOOSTER PUMP indicator (green) (L2)
Indicates that booster service pump P2
is ON, press to test
8
Booster pump HAND/OFF/AUTO (SW2)
3-position selector switch to turn on/off
booster service pump P2
9
BACKWASH PUMP indicator (green) (L3)
Indicates that backwash service pump
P3 is ON, press to test
10
Backwash pump ON/OFF/AUTO (SW3)
3-position selector switch to turn on/off
backwash service pump P2
11
DISTRIBUTION PUMP indicator (green) (L4)
Indicates that distribution service pump
P8 is ON, press to test
12
Distribution pump OFF/ON switch (SW4)
2-position selector switch to turn on/off
distribution service pump P8
13
HIGH PRESSURE SHUTDOWN indicator (red)
Indicates that high-pressure plunger
(L7)
pump P4 has been turned off because
of pressure greater than 125 psi
14
RESET pushbutton switch (SW7) (black)
Pushbutton to reset high pressure
shutdown
15
HEATER indicator (green) (L8)
Indicates that the heater for heating the
cleaning solution is ON, press to test
16
Heater OFF/ON switch (SW11)
2-position selector switch to turn on/off
heater for the cleaning tank
17
EMERGENCY STOP (red) (SW9)
Push pull button to turn off the LWP
electrical system
18
Hour meter (HM1) (0 to 99999.9)
Cumulative time in hours of the
operation of the high-pressure pump
on the high-pressure pump module
There are nine power receptacles on the control module for the LWP modules, heater, 3kW TQG set, and
service pump cables are shown in Figure 2 and Figure 3, and described in Table 2.