TM 10-4610-310-14
0004 00
CONTROL MODULE - continued
KEY
CONTROL OR INDICATOR
FUNCTION
1
Jam nut receptacle (4 wire) for 3kW Tactical Quiet
Generator set power cable 1. Includes protective
cover
2
J4 BACKWASH PUMP
Jam nut receptacle (3 wire) for backwash service
pump P3 power cable 4. Includes protective cover
3
J5 DISTRIBUTION PUMP
Jam nut receptacle (3 wire) for distribution service
pump P8 power cable 5. Includes protective cover
4
J8 CHEMICAL MODULE
Jam nut receptacle (4 wire) for chemical
injection/cleaning module power cable 8. Includes
protective cover
5
J6 FILTRATION MODULE
Jam nut receptacle (10 wire) for ultrafiltration
module power cable 6. Includes protective cover
6
J3 BOOSTER PUMP
Jam nut receptacle (3 wire) for booster service
pump P2 power cable 3. Includes protective cover
7
J7 HP PUMP MODULE
Jam nut receptacle (6 wire) for high-pressure
pump module power cable 7. Includes protective
cover
8
J2 RAW WATER PUMP
Jam nut receptacle (3 wire) for raw water service
pump P1 power cable 2. Includes protective cover
9
J9 HEATER
Jam nut receptacle (3 wire) for immersion heater
power cable 9. Includes protective cover
Internal Electronic Components
The internal electronic components to the control module interface with the switches and indicators on the
control panel and remote components of the LWP and are shown in Figure 4, Figure 5, and described in Table 3.
The internal electronic components consist of:
Four start modules for raw water, booster, backwash, and distribution service pumps
Twenty-one surge protectors, three locations for incoming power, service pumps, heater, and PLC
input/output leads
Three circuit breakers, one 20 ampere interfacing with enclosure handle, one 10 ampere for control
power, and one 10 ampere for heater
One programmable logic controller
One terminal board
One control relay for the heater
Three motor controllers for booster, backwash, and distribution service pumps