TM 10-4610-310-14
0081 00
CORRECTIVE
MALFUNCTION
TEST/INSPECTION
ACTION
If voltage is present and no fault is
found at receptacle assembly,
1. Ensure that the raw water
Replace distribution
pump and cable is
pump if motor starter
serviceable.
module for the
2. Connect the raw water
distribution pump (M4)
pump cable to the
trips
distribution pump.
3. Turn on the raw water
pump switch
Inspect pump switch.
Inspect surge protector SP 5
Replace if voltage is
present at the input
Check for 240 VAC at the input
and not at the output
(between wires 78 and 79) and
output (between wires 95 and 97).
Inspect soft starter SS3
Replace if voltage is
present at the input
With power on, check for 240 VAC
and not at the output
2. Pump light is on but pump is not operating
at the input (between wires 88 and
- continued
89) and output (between wires 78
and 79).
Inspect motor controller module
Replace if voltage is
M4
present at the input
and not at the output
With power on, check for 240 VAC
at the input (between wires 60 and
61) and output (between wires 88
and 89).
proper wire connections.
cable wires from the
generator and
reconnect them
securely.
0081 00-2