TM 55-1930-209-14&P-1
a.
Select EDIT MENU option 1 to activate/deactivate sensors by pushing keyboard key 1. Following prompt
appears on screen:
SELECT PAGE TO EDIT
BY PRESSING CORRESPONDING KEY
OR PRESS EDIT KEY TO RETURN TO THE MENU
NOTE
If display page that shows a bargraph is pressed, highlighted instructions called
"prompts" show in the right corner or across top of video monitor and cursor
highlights top bargraph. If a display page without a bargraph is selected, page will
flash and monitor returns to menu shown above. Push either another display page
key or EDIT key.
b.
Push key of display page that shows a bargraph, such as POTABLE WATER TANKS (Figure 8-3) or
CHLORINE STATUS (Figure 8-9). Make sure selected display page shows on video monitor.
c.
If following prompts show on screen and cursor appears over first bargraph, go to step e.
1
-
ADVANCE CURSOR
2
-
EDIT THIS ONE
3
-
SELECT NEW PAGE
4
-
RETURN TO EDIT MENU
d.
If screen flashes, indicating display page does not have sensor readouts, either press another display
page key or press EDIT key to return to edit menu.
NOTE
Cursor is a bright bar that extends from left side to middle of screen and highlights
an item to be edited. Pushing keyboard key 1 (prompt ADVANCE CURSOR) moves
cursor one line down. Repeatedly pushing this key or holding it down moves
cursor to the last line that can be edited, and then cursor returns to top line.
e.
Push keyboard key 1 (ADVANCE CURSOR) and move cursor to desired sensor bargraph.
f.
Push keyboard key 2 (EDIT THIS ONE). Make sure video monitor displays desired sensor information
with sensor label on top line and prompts in upper right comer. Also make sure that cursor is on the line
with "SENSOR ACTIVE."
g.
Push keyboard key 2 (EDIT THIS ONE) again. Make sure cursor extends all the way to the right.
h.
To activate sensor, push keyboard key "0" and to deactivate sensor, push keyboard key 1.
i.
Push ENTER keyboard key. Note that cursor will shorten.
NOTE
EXIT keyboard key provides means to immediately leave edit mode at any time.
When EXIT key is pressed, EDIT key goes out and EMS resumes scanning.
j.
If editing is complete, push EDIT keyboard key to leave edit mode and return EMS video monitor to normal
scanning. If editing is not completed, push keyboard key 3 (prompt SELECT NEW BAR) to return to
display page.
8-20