TM 55-1930-209-14&P-1
13-12.2.2 Emergency shutdown procedures
a.
Local emergency ROWPU shutdown. Pull emergency shutdown cord surrounding diesel engine (Figure 13-7, 1
of 2) to stop engine and HP pump.
b.
Remote emergency ROWPU shutdown. Push appropriate system shutdown button, either "ROWPU 1 diesel HP
pump" or "ROWPU 2 diesel HP pump" on starboard side of ROWPU space near personnel door. This stops the
ROWPU HP pump but not the seawater pump feeding that ROWPU system. If this shutdown is used, immediate
action must be taken to turn off the appropriate seawater pump.
c.
Remote total system shutdown. Push any total shutdown red button to stop all pumps (Chapter 3).
d.
When the situation that caused the emergency has been corrected, reset emergency button by turning collar
behind button one-quarter turn clockwise. Button will pop out and again be in the ready position.
e.
When emergency button is reset, any systems turned off by that emergency button must be restarted with their
individual controls.
13-34