TM 55-1930-209-14&P-19
Table 3-3. Preventive Maintenance Checks and Services for ROWPU System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
(e) Empty and dean glass collecting
bowl on bottom d engine
crankcase filter system s fold-
lows:
Pull down on metal tab of
cage surrounding bowl.
Unsnap wire cage on each
side of bottom of bowl.
Remove bowl and wipe with
dean cloth. Do not use abra-
sives.
Replace fuel filter in reverse
order.
81
Pump V Belts
WARNING
To prevent electric shock, ensure battery
Is disconnected before performing this
procedure.
NOTE
Refer to TM 55-1930-209-14&P-2, para
6.2.10 for complete Instructions and
Illustrations on belt tensioning.
a. Check tension on pump V-belts. If they
appear to be slack adjust tension.
1) Adjust HP pump Vet as
follows:
Remove 32 mounting bolts and
Iockwashers. Remove front V-belt
housing (two pieces).
Place a straight edge on V-belt in a
straight line with bearing bases.
Place tension meter pointer on the
line on the center of the front belt
NOTE
Do not contact O-ring on tester stern.
3-32 Change 1