TM 55-1930-209-14&P-19
Table 3-3. Preventive Maintenance Checks and Services for ROWPU System (Continued)
B -
Before
D -
Daily
Q - Quarterly
D -
During
W -
Weekly
S - Semiannually
A -
After
M -
Monthly
A - Annually
INTERVAL
ITEM
PROCEDURES
EQUIPMENT
ITEM
TO BE
CHECK FOR AND HAVE
IS NOT READY/
NO.
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
B D A D W M Q S A
AS NECESSARY
2) Press down on tester stem until regis-
ter flange just contacts the next belt.
3) Release pressure and note pressure
scale reading under O-ring.
4) Repeat steps (1) thru (2) for each belt.
5) Both readings should be 13-17 lb (9.5-
11.25 kg) and outside belts should be
within 1 lb (0.45 kg) of each other.
6) h belts are not adjusted correctly, pro-
ceed as follows:
Loosen four bolts.
Loosen two adjusting screw lock-
nuts.
Turn adjusting screws equally to
adjust belt tensioner assembly.
Check adjustments.
Tighten adjusting screw locknuts.
Tighten four bolts.
7) Check adjustment after 2 hours of
operation. Adjust as necessary.
Check again after 2 more hours of
operation. Install front Vbelt housing
(two pieces). Install 32 mounting bolts
and lockwashers.
b. Check for frayed or cracked HP pump
V-belts cracked
V-belts. If necessary, replace as follows:
or frayed.
NOTE
When one V-belt requires changing, replace
all 12 belts as a set.
1) Housing removal
(a) Remove 32 mounting bolts and
lockwashers.
(b) Remove front V-belt housing
(two pieces).
Change 1 3-33