2.The Light Module (LM-4)a.Basic module connections and jumper selections.b.Connections:1)Connect high water temperature device to terminal 1 either B+ or B-.2)Connect low oil pressure engine device to terminal 2 through OPR time delay contact in theAutostart. (See-Autostart Module: Item A.)3)Connect overspeed engine device to terminal 3 either B+ or B-.4)Connect overcrank from terminal 29 of the Autostart to terminal 4.5)Connect common failure output terminal 5 to common failure input on the Autostart terminal10.6)Connect B+ to terminal 7.7)Connect B- to terminal 6.8)Connect the respective lights to terminals 22, 23, & 25 as shown on the diagram. Connect theother side of the lights to B+ or terminal 27. (When terminal 27 is not being used for lamp test-see LAMP TEST JUMPER.)9)Connect the alarm horn to terminal 26 through a normally closed push-button as shown on thediagram.c.Jumper Selection:Each jumper is marked 1, 2, 3, 4 to correspond to input signals at terminals 1, 2, 3, 4respectively.L 1, 2, 3, 4 GREEN INSULATED JUMPER. When in place the Light Module will lock-in onthat corresponding signal input and require system reset before the light will go out. Whenclipped cut the corresponding light will go on and off with the input signal.PAGE 8