TM 10-4610-232-12
Table 4-1. Unit Preventive Maintenance Checks and Services
Item
No.
Interval
Item To Be
Check Or
Service
Procedure
Not Mission
Capable If:
(4) Inside compartments for
signs of water leakage.
(5) Latches operation, tight door
closures and loose mounting
hardware.
(6) Loose or missing doors/cabinet
ground connections.
Any ground strap or strap
mount screw missing.
c. Check for loose mounting
screws on panel and boxes.
d. Inspect for loose or missing
Ground wire or wire
ground wire and mount screw from
mounting screw missing.
main control panel to back wall.
20.
Semi
Generator Set,
Perform unit level PMCS in
Any fault listed in the Not
Annual
60 Kw
accordance with TM5-6115-545-12 or
Mission Capable column of
TM9-6115-645-10.
the generator TM.
21.
Semi
Storage Tanks,
Perform unit level PMCS in
Any fault listed in the Not
Annual
3,000 Gallon
accordance with
Mission Capable column of
TM5-5430-225-12&P.
the storage tank TM.
NOTE
The
following
checks
and
services must be performed by
DS
maintenance
personnel.
They must be scheduled by Unit
TAMMS clerk or maintenance
supervisor and work request
submitted to supporting DS or
TMDE shop.
22.
Semi
Trailer, 22.5 Ton
Perform unit level PMCS in
Any fault listed in the Not
Annual
accordance with TM9-2330-358-14
Mission Capable column of
or TM9-2330-386-14&P.
the trailer TM.
23.
12,000
Butterfly Valves
Replace valve liners in the manual,
Hours
automatic, cartridge filter block, feed
and cleaning bypass valves (para. 4-47).
24.
Semi
Air System
Notify DS maintenance to pressure
Annual
test the air storage tank.
25.
Semi
Flowmeter
Notify DS maintenance to check
Any flowmeter fails
Annual
accuracy of flowmeters.
accuracy.
26.
Annual
Generator
Notify DS maintenance to replace
generator mount noise pads.
27.
Annual
Pressure Gages
Notify DS to check accuracy of all
Any pressure gage fails
pressure gages.
accuracy test.
Change 12 4-11