TM 10-4610-232-34Table 2-1. Direct Support Troubleshooting Guide (Continued)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTIONCHLORINE MIXER.1. Chlorine mixer does not work. (Ref. Schematic diagram FO-1, sheet 8, schematic line 820).Shut down ROWPU and generator. Refer to the electrical drawings in Appendix D. Check continuity, point-to-pointT1(X1) (REF: Interconnection diagram FO-2, Sheet 10) to J12B, Repeat the procedure from T1(2X) to J12J (REF:Interconnection diagram FO-2, Sheet 9).(a) Repair any loose or damaged wire (para. 2-20).(b) Replace circuit breaker CB7 or CB9 (REF: Interconnection diagram FO-2, Sheet 8) if open (para.2-23).(c) Replace switch PB3 (REF: Interconnection diagram FO-2, Sheet 11) if open (para. 2-22).(d) Replace/repair connector J12 if faulty (para. 2-21).CIRCUIT BREAKERS. 1. Control circuit breaker (115 VAC) keeps tripping.Step 7.Step 2.Step 3.Step 4.Shut down ROWPU and generator. Refer to electrical drawings in Appendix D and determine which breakerkeeps tripping.Reset circuit breaker. If breaker wil not stay set, replace breaker (para. 2-23).Isolate portion of circuit which is grounded by disconnecting each connector attached to the control panelwhich ties back to the affected breaker. Panel must be powered up for this step.NOTECircuit breakers 11,13 and 14 (REF: Interconnection diagram FO-2, Sheet 8) are groundfault breakers, High humidity or moisture around devices controlled by these breakersmay occasionally cause trouble. Check that atmospheric moisture is not causing thetripping, by drying out anything controlled by these breakers.If the breakers stay set when a particular connector is disconnected, check the devices attached to thatconnector, which are controlled by the affected circuit breaker for short circuits.Replace/repair any defective component or wire found to be shorted.Shut down ROWPU and generator. Refer to the electrical schematic drawings in Appendix D and checkthrough the portion of the affected circuits which are internal to the control panel until the short circuit isfound.(a) Replace/repair any component or wire that is found to be shorted.(b) Replace the faulty circuit breaker if no shorts can be found (para. 2-23).2. Circuit breaker (440 VAC) will not reset.Step 1. Shut down ROWPU and the generator.Reset the breaker. If the breaker will not reset, replace the breaker (para. 2-25).Step 2. Refer to the electrical schematics in Appendix D. Check for short circuits in the circuits that the breakercontrols both between phases and to ground.(a) Repair any loose or damaged wire in the control panel (para. 2-20).(b) Replace/repair any shorted cable assemblies (para. 2-18 or unit maintenance).(c) Replace/repair any component that is shorted.(d) Replace the breaker if the above steps do not locate the problem (para. 2-25).3. Circuit breaker trips whenever its circuit is activated.Verify problem.Refer to malfunction 2 for corrective action.Change 12-13
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business