TM 10-4610-239-24
TM 08580B-24/3
REMOVAL.. (Cont)
b.
Remove tube (3) and adapter (4).
c.
Loosen clamp (5) and remove tubing (6) and adapter (7).
d.
Remove two bolts (8), two lockwashers (9), two flat washers (10), clamp (11), Nomex tape (12), and plate (13).
Discard lockwashers.
e.
Remove pipe section (2) and check valve (14) from pipe section (15).
f.
Remove check valve (14) from pipe section (2).
INSTALLATION.
NOTE
Apply antiseize tape to all male pipe threads before installation.
a.
Install check valve (14) on end of pipe section (2) nearest threaded adapter (4). Ensure arrow on check valve
points toward pipe section (2).
b.
Wrap pipe section (2) with Nomex tape (12).
c.
Install pipe section (2) and check valve (14) on pipe section (15). Ensure threaded adapter (4) points toward
multimedia filter and hose adapter (7) points upward.
d.
Position plate (13).
CAUTION
Pipe section can be badly damaged by corrosion if it is installed in contact with plate or
clamp. Be sure to separate pipe section from plate and clamp with Nomex tape.
e.
Install clamp (11), two flat washers (10), two lockwashers (9), and two bolts (8).
f.
Install adapter (7) and tubing (6) and tighten clamp (5).
g.
Install adapter (4) and tube (3).
h.
Install nipple (1) in pipe section (2).
2-263