TM 10-4610-241-10
TO 40W4-13-41
Table 2-2. Operator Preventive Maintenance Checks and Services
Location
Item To Check/
Service
Procedure
Not Fully Mission
Capable If:
Flatbed Cargo
Trailer
a.
Inspect hoses for leaks.
b. Check leveling jacks for proper
operation.
Any air leaks
Leveling Jacks inoperable
Ground Rods and
Grounding Stud
Inspect Ground Rods and Grounding
Stud for proper installation and loose
connections.
Ground rods or grounding studs
improperly installed or any loose
connections
Raw Water System
a. Check Raw Water Pump and
couplings for leaks
Class III leaks
b. Check pump Electric Motor for
discoloration and excessive noise.
c. Inspect Hoses for leaks
d. Inspect Electric Power Cables for
tears. burrs and cuts.
Steady stream of water
Any tears, buffs or cuts
Backwash System
a. Check Backwash Pump, Strainer and
Couplings for leaks.
Class III leaks
b. Check Pump Electric Motor for
discoloration and excessive noise.
c. Inspect Hoses for leaks.
d. Inspect Electric Power Cables for
tears, burrs and cuts.
Steady stream of water
Any tears, buffs or cuts
e. Check Backwash Tank for leaks.
In Accordance With TM 5-5430-
227-12&P
Product Water
system
a. Check Distribution Pump and
Couplings for leaks.
Class III leaks
b. Check Pump Electric Motor for
discoloration and excessive noise.
c. Inspect Hoses for leaks.
d. Inspect Electric Power Cables for
tears. buffs and cuts.
Steady stream of water
Any tears, burrs or cuts
e. Check Product Water Tanks for
leaks.
In Accordance With TM 5-5430-
277-12&P
Item
No.
3
4
5
6
7
Interval
During
During
During
During
During
2-28