TM 10-4610-246-13
4.16
MAINTENANCE INLET PIPE ASSEMBLY (cont)
c.
Repair.
Repair is accomplished by replacement of defective parts.
d.
Assembly.
(1)
Assemble reducing coupling, pressure gauge and water supply valve as follows:
(a)
Install reducer coupling (5, Figure 4-3) onto ratio-feeder assembly inlet (6).
(b)
Install straight adapter (4) and reducing tee (3).
(c)
Install straight adapter (2) and pipe tee (1) onto reducing tee (3).
(d)
Install pressure gauge (5, Figure 4-2) into pipe tee (6).
(e)
Install straight pipe adapter (4) and water supply ball valve (3) into pipe tee (6).
(f)
Connect water supply hose (2) to water supply ball valve (3) and tighten hose clamp (1).
(2)
Install strainer and ball valve as follows:
(a)
Install straight pipe adapter (9, Figure 4-1) into reducing tee (10).
(b)
Install strainer (7), pipe elbow (8), and straight pipe adapter (6).
(c)
Install ball valve (3) onto straight pipe adapter (6).
(d)
Install pipe elbow (5) into ball valve (3).
(e)
Install straight adapter (4) into pipe elbow (5).
Do not overtighten or damage to manifold assembly will occur.
(f)
Install straight adaptor (11) into manifold (12).
(g)
Connect nonmetallic hose (2) with hose clamps (1) to straight adapter (4). Tighten hose clamps
(1).
4-10