ARMY TM 10-4610-309-14
MARINE CORPS TM10802A-14/1
0035 00
TACTICAL WATER PURIFICATION SYSTEM (TWPS)
TROUBLESHOOTING PROCEDURES
UNIT TROUBLESHOOTING - TWPS CONTROL SYSTEMS
Table 3. OCP Miscellaneous Control Troubleshooting Continued.
ITEM
MALFUNCTION
POSSIBLE CAUSES
CORRECTIVE ACTION
3
Initial drain failures to occur
SV-903 failure.
Return to standby. Step through the BIT test
cont
when MF Clean Switch is set
to the test for SV-903. If the valve fails to
to Drain #1.
PLC Slot 3 input card or MF Clean
Open the OCP display panel to expose the
(Rotary) Switch failure.
sub-panel. Locate the Slot 3 card. Set the
MF Clean switch to Drain #1.
1) If the channel 4 light is ON, replace the
2) If the channel 4 light is OFF, open the
wire way and check for AC-Volts
between terminal IN4 and ground. If
there is voltage, replace the Slot 3 input
3) If there is no voltage, replace the MF
Clean cycle does not
PLC Slot 3 input card or MF Clean
Open the OCP display panel to expose the
automatically start the RO
(Rotary) Switch failure.
sub-panel. Locate the Slot 3 card. Set the
Feed Pump and fill the MF
MF Clean switch to Fill/Recirc.
when the MF Clean Switch is
1) If the channel 3 and 4 lights are ON,
set to Fill/Recirc.
replace the Slot 3 input card (WP
2) If the channel 3 or 4 light is OFF, open
the wire way and check for AC-Volts
between terminals IN3 or IN4 and
ground. If there is voltage, replace the
3) If there is no voltage, replace the MF
RO Feed Pump does not stop
PLC Slot 3 input card or MF Clean
Open the OCP display panel to expose the
when the MF Clean Switch is
(Rotary) Switch failure.
sub-panel. Locate the Slot 3 card. Set the
set to Soak.
MF Clean switch to Soak.
1) If the channel 5 light is ON, replace the
2) If the channel 5 light is OFF, open the
wire way and check for AC-Volts
between terminal IN5 and ground. If
there is voltage, replace the Slot 3 input
3) If there is no voltage, replace the MF
0035 00-17